Vacuum System
Vacuum central station consists of one, two or three vacuum pumps. The vacuum system is design to operate according to BS HTM 2022, EN 737-3, ISO 7396-1 standards. The duty vacuum pump is rated at 100% of the installation design flow rate and a standby pump capable of automatic operation is fitted (if needed). The vacuum plant design is enable isolation of any one component without interrupting system operation.
-
The vacuum center usually incorporates the following elements:
- One or two or three blade type rotary vacuum pumps, with inlet filter, air cooling, internal oil circulation, oil mist eliminator for oil-free exhaust air. Suction capacities from 12 m3/h to 600 m3/h.
- Vacuum tank, capacity according with pumps load.
- Electronic control panel for controlling the operation of the pumps
- Electrical panel for driving the pumps
- Vacuum sensors transducer 4-20mA and digital sensor (optional) for operation
- Vacuum gauges 0-760 mm Hg.
- No-return valves.
- Anti-bacterial filters 99,999% efficient according BS 3928, with differential pressure indicator and sterilisable drain flask.
- Sectioning valves.
- Distance alarm.